This document describes about Model ALP111 PROFIBUS-DP communication module (for FIO) that enables to operate PROFIBUS-DP master devices and exchange data with PROFIBUS-DP devices. This PROFIBUS-DP
communication module can be mounted on field control units (AFV30 £, AFV40£, AFV10£, and AFF50 £), ESB
bus node unit (ANB10 £), optical ESB bus node unit (ANB11 £), and ER bus node unit (ANR10 £).
ALP111 module has been certified by PROFIBUS Nutzerorganisation e.V. as complying with the PROFIBUS DP-V0.
ALP111-S00
ALP111-S01
Item Specifications
Model ALP111
Interface PROFIBUS-DP
Connection method EIA-RS-485-compliant
Signal isolation Isolated
Transmission speed 9600 bps to 12 Mbps
Transmission route Shielded
Maximum transmission distance 1.2 km per segment (at the communication speed of 9600 bps).
No. of communication port One port (*1)
Communication port D-sub 9 pin (female) (*2)
Maintenance port D-sub 9 pin (male), Interface: RS-232C
Maximum current consumption 0.7 A
Weight 0.3 kg
Note: The cables and terminators must comply with PROFIBUS-DP standards (PROFIBUS Specifications IEC 61158-2/EN 50170 volume 2).
*1: There is another port for maintenance.
*2: PROFIBUS-DP connector must comply with the PROFIBUS-Specificaiton-Normative-parts-2.